ntz210n-ph2

NTZ-210N-PH    pH Module

PH Interface for measuring and checking the pH, by simply connecting a pH electrode.

The moment the interface is connected, it will automatically be identified by the system “Plug & Play” as well as enable the relevant configuration menu.

Technical specifications
MEASURING RANGE from 0 to 14 pH
MEASURING RESOLUTION 0,01 pH
HYSTERESIS Set by user
ALARMS Audio and visual with thresholds set by user
CALIBRATION 2-point semi-automatic
ntz210n-rx2

NTZ-210N-RX    Redox Module

Redox Interface for measuring and checking the ORP value (Oxide-Reduction Potential) in by connecting a ORP electrode.

The moment the interface is connected, it will automatically be identified by the system “Plug & Play” as well as enable the relevant configuration menu.

Technical specifications
MEASURING RANGE from – 0mV to 1400mV
MEASURING RESOLUTION 1 mV
HYSTERESIS Set by user
ALARMS Audio and visual with thresholds set by user
CALIBRATION 2-point semi-automatic
ntz210n-ec

NTZ-210N-EC    EC Module

The conductivity interface is used to measure and control the conductivity value in   water through the connection of the EC NITZAN electrode.

The moment the interface is connected, it will automatically be identified by the system “Plug & Play” as well as enable the relevant configuration menu.

Technical specifications
MEASURING RANGE from 0 mS to 15 mS
MEASURING RESOLUTION 0,1mS
HYSTERESIS Set by user
ALARMS Audio and visual with thresholds set by user
CALIBRATION 1-point semi-automatic
COMPENSATION TEMPERATURE from 5° to 35°C
ntz210n-o2

NTZ-210N-O2   Oxygen Module

Dissolved Oxygen Interface is used to measure and control the value of dissolved oxygen in water (O2), through the connection of the O2 NITZAN Electrode. The moment the interface is connected, it will automatically be identified by the system “Plug & Play” as well as enable the relevant configuration menu.

Technical specifications
MEASURING RANGE 0-15 ppm / 0-120%
MEASURING RESOLUTION 1 % or 0.1  ppm
TEMPERATURE COMPENSATION With  PT100
ALARMS Audio and visual with thresholds set by user
CALIBRATION 2 points
ntz310n-fw2

NTZ-210N-FW    Flow Meter Module

Flow meter module  is used to measure and control the water flow in pipes of different diameter   through the connection with NITZAN flow sensor
With the same sensor, it is possible to have the flow and the liter counter measurement .
The moment the interface is connected, it will automatically be identified by the system “Plug & Play” as well as enable the relevant configuration menu.

Technical specifications
MEASURING RESOLUTION 0,1 lt/hr
ALARMS Audio and visual with thresholds set by use
CALIBRATION 1 point
KIND OF SENSOR With square  wave or free contact